 DC Current Signal Splitters |  | DRSP-I Series |  |  
  |  |  
| 
	|  |  |   
    |  |  | 
    
    	| ¥
	   6,185.00
         DRSP-I 
 |  |     
		       
		     
		        |  | One 4 to 20 mA Input to Two 4 to 20 mA Outputs with Full Isolation 
 |  
		        |  | Zero and Span Adjustments for Each Output 
 |  
		        |  | Full 1200 V Input/Output/ Power Isolation 
 |  
		        |  | Input/Output Loop Status LEDs 
 |  
		        |  | Output Test Button for Each Channel 
 |  
		        |  | Built-In Loop Power Supplies for Sink/Source I/O 
 |  
		        |  | Split, Convert, Boost, and Rescale Process Signals 
 |  
		        |  | Split Process Signals for Control and Validation 
 |  
		        |  | Interface a Process Signal with Multiple Panel Meters, PLCs, Recorders, Data Acquisition, DCS, and SCADA Systems 
 |  
		  	| View related products - Process Measurement and Control Instruments
 
 
 |  |  |  |  
	
	
|  |  
	| 
	
		|  | 
    	
      	| The DRSP-I Series DC current
signal splitters accept one 4 to
20 mA current input and provide two
optically isolated 4 to 20 mA current
outputs that are linearly related to
the 4 to 20 mA current input. This
provides an economical solution
when one signal must be sent to two
different devices.
Typical applications include
isolation, output splitting, output
device separation and redundancy
(i.e. to prevent failure of the entire
loop if one device fails), or a
combination of these.
The input signal is filtered, amplified,
split, and then passed through an
opto-coupler to the output stages.
Full 4-way isolation (input, output 1,
output 2, power) make this module
useful for ground loop elimination,
common mode signal rejection,and
noise pickup reduction.
 
 Specifications
 Input
 Input Range: 4 to 20 mA
 Input Impedance: 50 Ω typical
 Input Loop Power Supply: 15 Vdc ±10%, regulated, 25 mA; May be selectively wired for sinking or sourcing mA input
 Loop Status LEDs: Variable brightness LEDs indicate I/O loop level and status; One for input, one for each output
 Output
 Output Range:
 (Output 1 and Output 2): 4 to 20 mA; 20V compliance, 1000 Ω at 20 mA
 Output Linearity: Better than ±0.1% of span
 Output Zero and Span: Multi-turn zero and span potentiometers for each output channel to compensate for load and lead variations; ±15% of span adjustment range typical
 Output Loop Power Supplies: One for each output channel; 20 Vdc nominal, regulated, 25 mA may be selectively wired for sinking or sourcing mA output
 Output Ripple and Noise: Less than 10 mVRMS
 Output Functional Test: Front buttons set each output to test level when pressed; Each test level potentiometer adjustable 0 to 100% of span
 General
 Response Time: 70 milliseconds typical
 Common Mode Rejection: 120 dB minimum
 Isolation (Full 4-Way Isolation): Input 1, output 1, output 2, power; 1200 VRMS minimum
 Ambient Temperature Range: -10 to 60°C (14 to 140°F)
 Stability: Better than ±0.04% of span per °C
 Power:
 DRSP-I: 60 to 265 Vac, 50/60 Hz or 85 to 300 Vdc, 6 W maximum
 DRSP-I-DC: 9 to 30 Vdc or 10 to 32 Vac 50/60 Hz, 6 W maximum
 Housing: IP40, mounts to standard 35 mm (1.37") DIN rail
 Connectors: Eight 4-terminal removable connectors; 14 AWG maximum wire size
 Dimensions: 45 W x 117 H x 122 mm D (1.78 x 4.62 x 4.81"); height includes connectors
 |  |  |  |  |  |  |  | | † Price are shown in RMB. 
 Note: Comes complete with operator’s manual.
 Ordering Example: (1) DRSP-I DC current signal splitter, 60 to 265 Vac, 50/60 Hz or 85 to 300 Vdc power, ¥6,185.00
 | 
 |  
	|  |  |  |  | 
 |  |  | 
	
	
		| Related Links - 
		  Related Products |  |  
		|  |  
		|  |  
		|  |  |  |