 3-1/2 Digit AC Power Line Monitor, 1/8 DIN |  | DP301AN-AC |  |  
  |  |  
| 
	|  |  |   
    | 
        
			| 3-1/2 Digit AC Power Line Monitor, 1/8 DIN 
  |          
           | Click for larger image. |  |  | 
    
    	|  |  |     
		       
		     
		        |  | 1,999 Count Display Span 
 |  
		        |  | 50.0 to 199.9 Vac Range (100 mV Resolution) 
 |  
		        |  | 50 to 650 Vac Range (1V Resolution) 
 |  
		        |  | Bright, 14 mm (0.56") LED Display 
 |  
		        |  | Automatic Zero 
 |  
		        |  | Display Hold and Test 
 |  
		        |  | Screw-Terminal Barrier Strip 
 |  
		        |  | Short 104 mm (4.1") DeeP 1/8 DIN Case 
 Options
 
 |  
		        |  | Isolated 9 to 32 Vdc Power 
 |  
		        |  | Isolated 26 to 56 Vdc Power 
 |  
		        |  | NEMA 4 (IP65) Splash Proof Lens Cover 
 |  
		        |  | NEMA 4 (IP65) Splash Proof Lens Case 
 |  
		  	| View related products - Process Measurement and Control Instruments
 
 
 |  |  |  |  
	
	
|  |  
	| 
	
		|  | 
    	
      	| The DP301AN-AC is a low-cost, compact 3-1/2 digit
panel meter for AC power line monitoring. It uses a
half-wave rectifier calibrated to read the RMS value of
sinusoidal signals.
 
 Two input ranges are jumper-selectable: 50.0 to
199.9 Vac with 100 mV resolution and accuracy
optimized for 115 Vac, and 50 to 650V with 1V
resolution and accuracy optimized for 230 Vac. The
meter fits a standard ¹/8 DIN panel cutout 92 x 45 mm
(3.62 x 1.77") and requires a depth of less than 104 mm
(4.1") behind the panel. A screw-terminal barrier strip
for signal and power is standard.
 
 Mechanical options include a board-edge connector
display TEST, display HOLD, +4.7V and -4.7V outputs
splash-proof lens cover which meets NEMA 4 (IP65)
requirement is available for industrial environments.
Power options isolated 9 to 32 Vdc and 26 to 56 Vdc.
 
 SPECIFICATIONS
 Noise Rejection (AC GND to SIG GND)
 CMR: 120 dB, DC to 60 Hz
 CMV: 1500 Vp per HV test, 354 Vp per IEC spacing
 Accuracy at 25°C (10 to 100% of Full-Scale Range)
 Maximum Error (Reading–Actual):
 50.0 to 199.9 V range: ±0.006 (R-115 V)
 ±0.1 V and 50 to 650 V range: ±0.006 (R-230 V) ±1 V
 Span Tempco: ±0.01% of reading/°C
 Step Response: 1 s
 Warmup to Rated Accuracy: 10 min
 Signal Input
 Configuration: Half-wave average, RMS-calibrated
 Zero: Automatic
 Frequency: 49 to 440 Hz
 Display
 Type: 7-segment, red LED
 Height: 14.2 mm (0.56")
 Symbols: 1.8.8.8
 Decimal Points: Three positions programmable internally or at connector, 10 mA average sink
 Overrange Indication: Three least-significant digits blank
 Power
 AC Voltages: 115 or 230 Vac ±15%
 AC Frequency: 49 to 440 Hz
 DC Voltages: 9 to 32 Vdc, isolated to 300 Vp; 26 to 56 Vdc, isolated to 300 Vp
 Power Consumption: 2.4 W (nominal)
 Output Voltages: 4.7 Vdc and -4.6 Vdc ±5%, 10 mA max
 Environmental
 Operating Temperature: 0 to 60°C
 Storage Temperature: -40 to 85°C
 Relative Humidity: 95% at 40°C (non-condensing)
 Analog-to-Digital Conversion
 Technique: Dual-slope, average-value
 Read Rate: 2.5/s
 Integration Period: 100 ms
 Digital Controls
 HOLD and TEST Inputs: TTL or 5 V CMOS compatible
 Mechanical
 Bezel: 96 W x 48 H x 5.1 mm D (3.78 x 1.89 x 0.20")
 Depth Behind Bezel: 104 mm (4.09")
 Panel Cutout: 92 W x 45 mm H (3.62 x 1.77")
 Weight: 14 oz (400 g)
 Case Material: 94V-0 UL-rated polycarbonate
 |  |  |  |  |  |  |  | | † Price are shown in RMB. 
 
 | 
 |  
	|  | 
	
		|  |  |  
		|  |  |  |  
		|  | Part Number Builder |  |  
		|  |  |  |  
		|  | 
		  
		    |  |   
		    | Option Descriptions |   
		    | (1) | Model |   
		    |  | Select DP301AN for  3-1/2 digit AC power line monitor
  
		    | (2) | Input Range |   
		    |  | Select -AC5 for 50 to 199.9 Vac (includes D4 connector)
 -AC6 for 50 to 650 Vac (includes D4 connector)
  
		    | (3) | Power options |   
		    |  | Select Nothing(leave field blank) for 115 Vac 50/60 Hz power
 -C1 for 230 Vac 50/60 Hz
 -C3C for Isolated 9 to 32 Vdc
 -C3E for  Isolated 26 to 56 Vdc
  
		    | (4) | Add-On Option |   
		    |  | Select Nothing(leave field blank) for red LED display
 -G for Green LED display
 |  
		      | NOTE: All combinations may not be valid, check spec sheet for valid part numbers. |  |  |  |  |  |  
		|  |  
 |  |  | 
 |  |  |  |  
	| 
  	
    	| Keywords:ac voltmeter,AC power line monitoring,Automatic Zero,1/8 DIN Meter 
 |  Back to top
  
 
 |  |  |